NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function No. PTC Relay
No Function [0] - -
Safe Stop Alarm [1]* - Safe Stop [A68]
Safe Stop Warning [3] - Safe Stop [W68]
PTC 1 Alarm [4] PTC 1 Safe Stop
[A71]
-
PTC 1 Warning [5] PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A [6] PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W [7] PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8] PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9] PTC 1 Safe Stop
[W71]
Safe Stop [A68]
Table 3.16
W means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Refer to in Table 5.3.
5-20 Terminal X46/1 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-21 Terminal X46/3 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-22 Terminal X46/5 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-23 Terminal X46/7 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-24 Terminal X46/9 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-25 Terminal X46/11 Digital Input
Option: Function:
[0] * No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
5-26 Terminal X46/13 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1* Digital Inputs
3.7.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals
27 and 29. Set the I/O function for terminal 27 in
5-01 Terminal 27 Mode, and set the I/O function for
terminal 29 in 5-02 Terminal 29 Mode.
NOTE
These parameters cannot be adjusted while the motor is
running.
[0] No operation
Default for all digital outputs and relay
outputs
[1] Control ready The control card is ready. E.g.: Feedback
from a frequency converter where the
control is supplied by an external 24 V
(MCB 107) and the main power to the
unit is not detected.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready /
remote control
The frequency converter is ready for
operation and is in [Auto On] mode.
[4] Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable).
No warnings are active.
[5] VLT running Motor is running and shaft torque
present.