EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 301

Danfoss VLT AutomationDrive FC 301 User Manual

Danfoss VLT AutomationDrive FC 301
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
NB!
When Freeze output is active, the frequency converter cannot be stopped via a
low ‘start [8]’ signal. Stop the frequency converter via a terminal programmed
for Coasting inverse [2] or Coast and reset, inverse.
[21] Speed up Select Speed up and Speed down if digital control of the up/down speed is desired (motor poten-
tiometer). Activate this function by selecting either Freeze reference or Freeze output. When Speed
up/ down is activated for less than 400 msec. the resulting reference will be increased/ decreased
by 0.1 %. If Speed up/ down is activated for more than 400 msec. the resulting reference will follow
the setting in ramping up/ down parameter 3-x1/ 3-x2.
Shut down Catch up
Unchanged speed 0 0
Reduced by %-value 10
Increased by %-value 0 1
Reduced by %-value 11
[22] Speed down Same as Speed up [21].
[23] Set-up select bit 0 Select Set-up select bit 0 or Select Set-up select bit 1 to select one of the four set-ups. Set
par. 0-10
Active Set-up
to Multi Set-up.
[24] Set-up select bit 1 (Default Digital input 32): Same as Set-up select bit 0 [23].
[26] Precise stop inv. Prolongs stop signal to give a precise stop independent of speed.
Sends an inverted stop signal when the precise stop function is activated in par. 1-83
Precise Stop
Function
.
Precise stop inverse function is available for terminals 18 or 19.
[27] Precise start, stop Use when Precise ramp stop [0] is selected in par 1-83.
[28] Catch up Increases reference value by percentage (relative) set in par. 3-12
Catch up/slow Down Value
.
[29] Slow down Reduces reference value by percentage (relative) set in par. 3-12
Catch up/slow Down Value
.
[30] Counter input Precise stop function in par. 1-83
Precise Stop Function
acts as Counter stop or speed compensated
counter stop with or without reset. The counter value must be set in par. 1-84
Precise Stop Counter
Value
.
[31] Pulse edge triggered Edge triggered pulse input counts number of pulse flanks per sample time. This gives a higher
resolution at high frequencies, but is not as precise at lower frequencies. Use this pulse principle
for encoders with very low resolution (e.g. 30 ppr).
[32] Pulse time based Time based pulse input measures the duration between flanks. This gives a higher resolution at
lower frequencies, but is not as precise at higher frequencies. This principle has a cut-off frequency
which makes it unsuited for encoders with very low resolutions (e.g. 30 ppr) at low speeds.
VLT
®
AutomationDrive FC 300 Operating
Instructions
4 How to Programme
MG.33.AG.02 - VLT
®
is a registered Danfoss trademark
61
4

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals