Figure 2.16 Installation to Achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1).
1
Safety device Cat. 3 (circuit interrupt device, possibly
with release input)
7 Inverter
2 Door contact 8 Motor
3 Contactor (Coast) 9 5V DC
4 Adjustable frequency drive 10 Safe channel
5 Line power 11 Short-circuit protected cable (if not inside installation cabinet)
6 Control board
Safe Stop Commissioning Test
After installation and before first operation, perform a commissioning test of the installation making use of safe stop.
Moreover, perform the test after each modification of the installation.