Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB839.10
Function Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 sec
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start Event
[19] Warning
13-02 Stop Event
[44] Reset
key
13-10 Comparato
r Operand
[21] Warning
no.
13-11 Comparato
r Operator
[1] ≈*
13-12 Comparato
r Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
* = Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and if
Warning 90 becomes TRUE,
then Relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 sec., then the drive
continues and the warning
disappears. But Relay 1 will still
be triggered until [Reset] on
the LCP.
Table 6.13 Using SLC to Set a Relay
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB841.10
Function Setting
5-40 Function
Relay
[32] Mech.
brake ctrl.
5-10 Terminal 18
Digital Input
[8] Start*
5-11 Terminal 19
Digital Input
[11] Start
reversing
1-71 Start Delay
0.2
1-72 Start
Function
[5] VVC+/
FLUX
Clockwise
1-76 Start
Current
Im,n
2-20 Release
Brake Current
App.
dependent
2-21 Activate
Brake Speed
[RPM]
Half of
nominal slip
of the motor
* = Default Value
Notes/comments:
Table 6.14 Mechanical Brake Control
Start (18)
Start
reversing (19)
Relay output
Speed
Time
Current
1-71
1-71
2-21
2-21
1-76
Open
Closed
130BB842.10
Application Set-Up Examples
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark 6-5
6 6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 303 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 303
CategoryDC Drives
LanguageEnglish

Related product manuals