Line Power Supply 3 x 200–240V AC
FC 301/FC 302 P15K P18K P22K P30K P37K
High/ Normal Load
1)
HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output [kW] 15 18.5 18.5 22 22 30 30 37 37 45
Enclosure IP20 B4 C3 C3 C4 C4
Enclosure IP21 C1 C1 C1 C1 C1
Enclosure IP55, 66 C1 C1 C1 C2 C2
Output current
Continuous
(3 x 200–240V) [A]
59.4 74.8 74.8 88 88 115 115 143 143 170
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
89.1 82.3 112 96.8 132 127 173 157 215 187
Continuous
kVA (208V AC) [kVA]
21.4 26.9 26.9 31.7 31.7 41.4 41.4 51.5 51.5 61.2
Max. input current
Continuous
(3 x 200–240V) [A]
54 68 68 80 80 104 104 130 130 154
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
81 74.8 102 88 120 114 156 143 195 169
Additional specifications
Max. cable size, IP20 [mm
2
(AWG)]
2)
35 (2) 90 (3/0) 90 (3/0) 120 (4/0) 120 (4/0)
Max. cable size, IP21/55/66
[mm
2
(AWG)]
2)
90 (3/0) 90 (3/0) 90 (3/0) 120 (4/0) 120 (4/0)
Max. cable size with line
power disconnect [mm
2
(AWG)]
2)
35 (2) 70 (3/0) 150 (MCM 300)
Estimated power loss
at rated max. load [W]
4)
624 737 740 845 874 1140 1143 1353 1400 1636
Weight,
enclosure IP21, IP 55, 66 [kg]
45 45 45 65 65
Efficiency
4)
0.96 0.97 0.97 0.97 0.97