NB!
Do not set par. 14-20
Reset Mode
, to [13] Infinite auto reset, when par. 22-60
Broken Belt Function
is set to [2] Trip. Doing so will
cause the drive to continuously cycle between running and stopping when a broken belt condition is detected.
NB!
If the drive is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the drive experiences
a persistent alarm condition, be sure to disable the bypass’s automatic bypass function, if [2] Trip is selected as the Broken Belt Function.
22-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Sets the broken belt torque as a percentage of the rated motor torque.
22-62 Broken Belt Delay
Range: Function:
10 s [0 - 600 s] Sets the time for which the Broken Belt conditions must be active before carrying out the action
selected in par. 22-60
Broken Belt Function
.
22-75 Short Cycle Protection
Option: Function:
[0] * Disabled Timer set in par. 22-76
Interval between Starts
is disabled.
[1] Enabled Timer set in par. 22-76
Interval between Starts
is enabled.
22-76 Interval between Starts
Range: Function:
Application
dependent*
[Application dependant] Sets the time desired as minimum time between two starts. Any normal start command (Start/Jog/
Freeze) will be disregarded until the timer has expired.
22-77 Minimum Run Time
Range: Function:
0 s* [Application dependant] Sets the time desired as minimum run time after a normal start command (Start/Jog/Freeze). Any
normal stop command will be disregarded until the set time has expired. The timer will start counting
following a normal start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock command.
NB!
Does not work in cascade mode.
6 How to Programme the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Operating In-
structions
118 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark
6

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL

Related product manuals