8.2 Filter Specifications
Frame size D E F
Voltage [V] 380 - 480 380 - 480 380 - 480
Current, RMS [A] 120 210 330 Nominal value
Peak Current [A] 340 595 935 Amplitude value of the current
RMS overload [%] No Overload 60 seconds in 10 min
Response time [ms] < 0.5
Settling time - reactive current control
[ms]
< 40
Settling time - harmonic current control
(filtering) [ms]
< 20
Overshoot - reactive current control [%] < 20
Overshoot - harmonic current control
[%]
< 10
Table 8.1: Power Ranges (LHD with AF)
8 General Specifications
VLT HVAC Low Harmonic Drive Operating In-
structions
168 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark