6.3.3 1-** Load / Motor
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
1-0* General Settings
1-00 Configuration Mode null All set-ups TRUE - Uint8
1-03 Torque Characteristics [3] Auto Energy Optim. VT All set-ups TRUE - Uint8
1-06 Clockwise Direction [0] Normal All set-ups FALSE - Uint8
1-2* Motor Data
1-20 Motor Power [kW] SR All set-ups FALSE 1 Uint32
1-21 Motor Power [HP] SR All set-ups FALSE -2 Uint32
1-22 Motor Voltage SR All set-ups FALSE 0 Uint16
1-23 Motor Frequency SR All set-ups FALSE 0 Uint16
1-24 Motor Current SR All set-ups FALSE -2 Uint32
1-25 Motor Nominal Speed SR All set-ups FALSE 67 Uint16
1-28 Motor Rotation Check [0] Off All set-ups FALSE - Uint8
1-29 Automatic Motor Adaptation (AMA) [0] Off All set-ups FALSE - Uint8
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs) SR All set-ups FALSE -4 Uint32
1-31 Rotor Resistance (Rr) SR All set-ups FALSE -4 Uint32
1-35 Main Reactance (Xh) SR All set-ups FALSE -4 Uint32
1-36 Iron Loss Resistance (Rfe) SR All set-ups FALSE -3 Uint32
1-39 Motor Poles SR All set-ups FALSE 0 Uint8
1-5* Load Indep. Setting
1-50 Motor Magnetisation at Zero Speed 100 % All set-ups TRUE 0 Uint16
1-51 Min Speed Normal Magnetising [RPM] SR All set-ups TRUE 67 Uint16
1-52 Min Speed Normal Magnetising [Hz] SR All set-ups TRUE -1 Uint16
1-58 Flystart Test Pulses Current 30 % All set-ups FALSE 0 Uint16
1-59 Flystart Test Pulses Frequency 200 % All set-ups FALSE 0 Uint16
1-6* Load Depen. Setting
1-60 Low Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-61 High Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-62 Slip Compensation 0 % All set-ups TRUE 0 Int16
1-63 Slip Compensation Time Constant SR All set-ups TRUE -2 Uint16
1-64 Resonance Dampening 100 % All set-ups TRUE 0 Uint16
1-65 Resonance Dampening Time Constant 5 ms All set-ups TRUE -3 Uint8
1-7* Start Adjustments
1-71 Start Delay 0.0 s All set-ups TRUE -1 Uint16
1-73 Flying Start [0] Disabled All set-ups TRUE - Uint8
1-77 Compressor Start Max Speed [RPM] SR All set-ups TRUE 67 Uint16
1-78 Compressor Start Max Speed [Hz] SR All set-ups TRUE -1 Uint16
1-79 Compressor Start Max Time to Trip 5.0 s All set-ups TRUE -1 Uint8
1-8* Stop Adjustments
1-80 Function at Stop [0] Coast All set-ups TRUE - Uint8
1-81 Min Speed for Function at Stop [RPM] SR All set-ups TRUE 67 Uint16
1-82 Min Speed for Function at Stop [Hz] SR All set-ups TRUE -1 Uint16
1-86 Trip Speed Low [RPM] SR All set-ups TRUE 67 Uint16
1-87 Trip Speed Low [Hz] SR All set-ups TRUE -1 Uint16
1-9* Motor Temperature
1-90 Motor Thermal Protection [4] ETR trip 1 All set-ups TRUE - Uint8
1-91 Motor External Fan [0] No All set-ups TRUE - Uint16
1-93 Thermistor Source [0] None All set-ups TRUE - Uint8
VLT HVAC Low Harmonic Drive Operating In-
structions 6 How to Programme the Low Harmonic Drive