6.4.2 Digital In/Out 5-**
Par.
No. #
Parameter description Default value 4-set-up FC 302
only
Change dur-
ing opera-
tion
Conver-
sion index
Type
5-0* Digital I/O mode
5-00 Digital I/O Mode [0] PNP All set-ups FALSE - Uint8
5-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint8
5-02 Terminal 29 Mode [0] Input All set-ups x TRUE - Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE - Uint8
5-11 Terminal 19 Digital Input [0] No operation All set-ups TRUE - Uint8
5-12 Terminal 27 Digital Input [0] No operation All set-ups TRUE - Uint8
5-13 Terminal 29 Digital Input [0] No operation All set-ups TRUE - Uint8
5-14 Terminal 32 Digital Input [90] AC Contactor All set-ups TRUE - Uint8
5-15 Terminal 33 Digital Input [91] DC Contactor All set-ups TRUE - Uint8
5-16 Terminal X30/2 Digital Input [0] No operation All set-ups TRUE - Uint8
5-17 Terminal X30/3 Digital Input [0] No operation All set-ups TRUE - Uint8
5-18 Terminal X30/4 Digital Input [0] No operation All set-ups TRUE - Uint8
5-19 Terminal 37 Safe Stop [1] Safe Stop Alarm 1 set-up TRUE - Uint8
5-20 Terminal X46/1 Digital Input [0] No operation All set-ups TRUE - Uint8
5-21 Terminal X46/3 Digital Input [0] No operation All set-ups TRUE - Uint8
5-22 Terminal X46/5 Digital Input [0] No operation All set-ups TRUE - Uint8
5-23 Terminal X46/7 Digital Input [0] No operation All set-ups TRUE - Uint8
5-24 Terminal X46/9 Digital Input [0] No operation All set-ups TRUE - Uint8
5-25 Terminal X46/11 Digital Input [0] No operation All set-ups TRUE - Uint8
5-26 Terminal X46/13 Digital Input [0] No operation All set-ups TRUE - Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE - Uint8
5-31 Terminal 29 Digital Output [0] No operation All set-ups x TRUE - Uint8
5-32 Term X30/6 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-33 Term X30/7 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-4* Relays
5-40 Function Relay [0] No operation All set-ups TRUE - Uint8
5-41 On Delay, Relay 0.30 s All set-ups TRUE -2 Uint16
5-42 Off Delay, Relay 0.30 s All set-ups TRUE -2 Uint16
6.4.3 Comm. and Options 8-**
Par.
No. #
Parameter description Default value 4-set-up FC 302
only
Change dur-
ing opera-
tion
Conver-
sion index
Type
8-0* General Settings
8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE - Uint8
8-02 Control Word Source null All set-ups TRUE - Uint8
8-03 Control Word Timeout Time 1.0 s 1 set-up TRUE -1 Uint32
8-04 Control Word Timeout Function [0] Off 1 set-up TRUE - Uint8
8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint8
8-06 Reset Control Word Timeout [0] Do not reset All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [1] FC MC 1 set-up TRUE - Uint8
8-31 Address 2 N/A 1 set-up TRUE 0 Uint8
8-32 FC Port Baud Rate [2] 9600 Baud 1 set-up TRUE - Uint8
8-35 Minimum Response Delay 10 ms All set-ups TRUE -3 Uint16
8-36 Max Response Delay 5000 ms 1 set-up TRUE -3 Uint16
8-37 Max Inter-Char Delay 25 ms 1 set-up TRUE -3 Uint16
8-5* Digital/Bus
8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8
VLT HVAC Low Harmonic Drive Operating In-
structions 6 How to Programme the Low Harmonic Drive
MG.16.A1.02 - VLT
®
is a registered Danfoss trademark 147