5.1.8 Quick Transfer of Parameter Settings when Using GLCP
Once the set-up of a frequency converter is complete, it is recommended to store (backup) the parameter settings in the GLCP or on a PC via MCT 10
Set-up Software Tool.
Stop the motor before performing any of these operations.
Data storage in LCP:
1. Go to par. 0-50
LCP Copy
2. Press the [OK] key
3. Select “All to LCP”
4. Press the [OK] key
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press [OK].
The GLCP can now be connected to another frequency converter and the parameter settings copied to this frequency converter.
Data transfer from LCP to Frequency converter:
1. Go to par. 0-50
LCP Copy
2. Press the [OK] key
3. Select “All from LCP”
4. Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press
[OK].
5.1.9 Initialisation to Default Settings
There are two ways to initialise the frequency converter to default: Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below description.
Recommended initialisation (via par. 14-22
Operation Mode
)
1. Select par. 14-22
Operation Mode
2. Press [OK]
3. Select “Initialisation” (for NLCP select “2”)
4. Press [OK]
5. Remove power to unit and wait for display to turn off.
6. Reconnect power and the frequency converter is reset. Note
that first start-up takes a few more seconds
7. Press [Reset]
Par. 14-22
Operation Mode
initialises all except:
Par. 14-50
RFI Filter
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Max Response Delay
Par. 8-37
Maximum Inter-Char Delay
Par. 15-00
Operating Hours
to par. 15-05
Over Volt's
Par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
Par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
NB!
Parameters selected in par. 0-25
My Personal Menu
, will stay present, with default factory setting.
Manual initialisation
5 How to Operate the Low Harmonic Drive