Q3-4 Application Settings
Q3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions
Par. 22-60 
Broken Belt Function
Par. 22-20 
Low Power Auto Set-up
Par. 1-03 
Torque Characteristics
Par. 22-61 
Broken Belt Torque
Par. 22-21 
Low Power Detection
Par. 1-71 
Start Delay
Par. 22-62 
Broken Belt Delay
Par. 22-22 
Low Speed Detection
Par. 22-75 
Short Cycle Protection
Par. 4-64 
Semi-Auto Bypass Set-up
Par. 22-23 
No-Flow Function
Par. 22-76 
Interval between Starts
Par. 1-03 
Torque Characteristics
Par. 22-24 
No-Flow Delay
Par. 22-77 
Minimum Run Time
Par. 22-22 
Low Speed Detection
Par. 22-40 
Minimum Run Time
Par. 5-01 
Terminal 27 Mode
Par. 22-23 
No-Flow Function
Par. 22-41 
Minimum Sleep Time
Par. 5-02 
Terminal 29 Mode
Par. 22-24 
No-Flow Delay
Par. 22-42 
Wake-up Speed [RPM]
Par. 5-12 
Terminal 27 Digital Input
Par. 22-40 
Minimum Run Time
Par. 22-43 
Wake-up Speed [Hz]
Par. 5-13 
Terminal 29 Digital Input
Par. 22-41 
Minimum Sleep Time
Par. 22-44 
Wake-up Ref./FB Difference
Par. 5-40 
Function Relay
Par. 22-42 
Wake-up Speed [RPM]
Par. 22-45 
Setpoint Boost
Par. 1-73 
Flying Start
Par. 22-43 
Wake-up Speed [Hz]
Par. 22-46 
Maximum Boost Time
Par. 1-86 
Trip Speed Low [RPM]
Par. 22-44 
Wake-up Ref./FB Difference
Par. 22-26 
Dry Pump Function
Par. 1-87 
Trip Speed Low [Hz]
Par. 22-45 
Setpoint Boost
Par. 22-27 
Dry Pump Delay
Par. 22-46 
Maximum Boost Time
Par. 22-80 
Flow Compensation
Par. 2-10 
Brake Function
Par. 22-81 
Square-linear Curve Approximation
Par. 2-16 
AC brake Max. Current
Par. 22-82 
Work Point Calculation
Par. 2-17 
Over-voltage Control
Par. 22-83 
Speed at No-Flow [RPM]
Par. 1-73 
Flying Start
Par. 22-84 
Speed at No-Flow [Hz]
Par. 1-71 
Start Delay
Par. 22-85 
Speed at Design Point [RPM]
Par. 1-80 
Function at Stop
Par. 22-86 
Speed at Design Point [Hz]
Par. 2-00 
DC Hold/Preheat Current
Par. 22-87 
Pressure at No-Flow Speed
Par. 4-10 
Motor Speed Direction
Par. 22-88 
Pressure at Rated Speed
Par. 22-89 
Flow at Design Point
Par. 22-90 
Flow at Rated Speed
Par. 1-03 
Torque Characteristics
Par. 1-73 
Flying Start
See also 
VLT HVAC Drive Programming Guide
 for a detailed description of the Function Setups parameter groups.
1-00  Configuration Mode
Option: Function:
[0] * Open Loop Motor speed is determined by applying a speed reference or by setting desired speed when in Hand
Mode.
Open Loop is also used if the frequency converter is part of a closed loop control system based on
an external PID controller providing a speed reference signal as output.
[3] Closed Loop Motor Speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed loop control process (e.g. constant pressure or flow). The PID controller
must be configured in par. 20-** or via the Function Setups accessed by pressing the [Quick Menus]
button.
NB!
This parameter cannot be changed when motor is running.
NB!
When set for Closed Loop, the commands Reversing and Start Reversing will not reverse the direction of the motor.
6 How to Programme the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Operating In-
structions
94 MG.16.A1.02 - VLT
®
 is a registered Danfoss trademark
6