EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 User Manual

Danfoss vlt FC 102
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
Q3-4 Application Settings
Q3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions
Par. 22-60
Broken Belt Function
Par. 22-20
Low Power Auto Set-up
Par. 1-03
Torque Characteristics
Par. 22-61
Broken Belt Torque
Par. 22-21
Low Power Detection
Par. 1-71
Start Delay
Par. 22-62
Broken Belt Delay
Par. 22-22
Low Speed Detection
Par. 22-75
Short Cycle Protection
Par. 4-64
Semi-Auto Bypass Set-up
Par. 22-23
No-Flow Function
Par. 22-76
Interval between Starts
Par. 1-03
Torque Characteristics
Par. 22-24
No-Flow Delay
Par. 22-77
Minimum Run Time
Par. 22-22
Low Speed Detection
Par. 22-40
Minimum Run Time
Par. 5-01
Terminal 27 Mode
Par. 22-23
No-Flow Function
Par. 22-41
Minimum Sleep Time
Par. 5-02
Terminal 29 Mode
Par. 22-24
No-Flow Delay
Par. 22-42
Wake-up Speed [RPM]
Par. 5-12
Terminal 27 Digital Input
Par. 22-40
Minimum Run Time
Par. 22-43
Wake-up Speed [Hz]
Par. 5-13
Terminal 29 Digital Input
Par. 22-41
Minimum Sleep Time
Par. 22-44
Wake-up Ref./FB Difference
Par. 5-40
Function Relay
Par. 22-42
Wake-up Speed [RPM]
Par. 22-45
Setpoint Boost
Par. 1-73
Flying Start
Par. 22-43
Wake-up Speed [Hz]
Par. 22-46
Maximum Boost Time
Par. 1-86
Trip Speed Low [RPM]
Par. 22-44
Wake-up Ref./FB Difference
Par. 22-26
Dry Pump Function
Par. 1-87
Trip Speed Low [Hz]
Par. 22-45
Setpoint Boost
Par. 22-27
Dry Pump Delay
Par. 22-46
Maximum Boost Time
Par. 22-80
Flow Compensation
Par. 2-10
Brake Function
Par. 22-81
Square-linear Curve Approximation
Par. 2-16
AC brake Max. Current
Par. 22-82
Work Point Calculation
Par. 2-17
Over-voltage Control
Par. 22-83
Speed at No-Flow [RPM]
Par. 1-73
Flying Start
Par. 22-84
Speed at No-Flow [Hz]
Par. 1-71
Start Delay
Par. 22-85
Speed at Design Point [RPM]
Par. 1-80
Function at Stop
Par. 22-86
Speed at Design Point [Hz]
Par. 2-00
DC Hold/Preheat Current
Par. 22-87
Pressure at No-Flow Speed
Par. 4-10
Motor Speed Direction
Par. 22-88
Pressure at Rated Speed
Par. 22-89
Flow at Design Point
Par. 22-90
Flow at Rated Speed
Par. 1-03
Torque Characteristics
Par. 1-73
Flying Start
See also
VLT HVAC Drive Programming Guide
for a detailed description of the Function Setups parameter groups.
1-00 Configuration Mode
Option: Function:
[0] * Open Loop Motor speed is determined by applying a speed reference or by setting desired speed when in Hand
Mode.
Open Loop is also used if the frequency converter is part of a closed loop control system based on
an external PID controller providing a speed reference signal as output.
[3] Closed Loop Motor Speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed loop control process (e.g. constant pressure or flow). The PID controller
must be configured in par. 20-** or via the Function Setups accessed by pressing the [Quick Menus]
button.
NB!
This parameter cannot be changed when motor is running.
NB!
When set for Closed Loop, the commands Reversing and Start Reversing will not reverse the direction of the motor.
6 How to Programme the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Operating In-
structions
94 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark
6

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals