Table 75: Wiring Conguration for Speed Up/Down
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e30bu076.10
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start*
Parameter 5-12 Terminal 27 Digital Input
[19] Freeze Reference
Parameter 5-13 Terminal 29 Digital Input
[21] Speed Up
Parameter 5-14 Terminal 32 Digital Input
[22] Speed Down
*=Deafult value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 29 in the parameter title corresponds to terminal XD2.15 in the control compartment.
Terminal 32 in the parameter title corresponds to terminal XD2.16 in the control compartment.
e30bu077.10
Speed
Reference
Start (XD2.12)
Freeze ref (XD2.14)
Speed up (XD2.15)
Speed down (XD2.16)
Illustration 58: Speed Up/Down
AQ357954340588en-000201 / 130R0881106 | Danfoss A/S © 2020.09
Wiring Conguration Examples
VLT® Refrigeration Drive FC 103
Operating Guide