EasyManuals Logo
Home>Danfoss>DC Drives>VLT FC 103

Danfoss VLT FC 103 User Manual

Danfoss VLT FC 103
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
-
-
-
9.3.2 WARNING 1, 10 Volts Low
Cause
The control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloa-
ded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.
Troubleshooting
Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace
the control card.
9.3.3 WARNING/ALARM 2, Live Zero Error
Cause
This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs
is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this
condition.
Troubleshooting
Check connections on all analog mains terminals.
Control card terminals 53 and 54 for signals, terminal 55 common.
VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common.
VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common.
Check that the drive programming and switch settings match the analog signal type.
Perform an input terminal signal test.
9.3.4 WARNING/ALARM 3, No Motor
Cause
No motor is connected to the output of the drive.
9.3.5 WARNING/ALARM 4, Mains Phase Loss
Cause
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input
rectier. Options are programmed in parameter 14-12 Function at Mains Imbalance.
Troubleshooting
Check the supply voltage and supply currents to the drive.
9.3.6 WARNING 5, DC Link Voltage High
Cause
The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
9.3.7 WARNING 6, DC Link Voltage Low
Cause
The DC-link voltage (DC) is lower than the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
9.3.8 WARNING/ALARM 7, DC Overvoltage
Cause
If the DC-link voltage exceeds the limit, the drive trips after a certain time.
Troubleshooting
Extend the ramp time.
Change the ramp type.
Activate the functions in parameter 2-10 Brake Function.
Increase parameter 14-26 Trip Delay at Inverter Fault.
If the alarm/warning occurs during a power sag, use kinetic back-up (parameter 14-10 Mains Failure).
Connect a brake resistor.
AQ357954340588en-000201 / 130R0881 | 123Danfoss A/S © 2020.09
Maintenance, Diagnostics, and
Troubleshooting
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals