0-37 Display Text 1
Range: Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication. Device ID can
be included.
Only used when running BACnet.
0-38 Display Text 2
Range: Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication.
Only used when running BACnet.
0-39 Display Text 3
Range: Function:
[0 - 0 ] Use this parameter to write an individual text string
to be read via serial communication.
Only used when running BACnet.
3.1.4 0-4* LCP
Enable, disable, and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled To avoid unintended start of the frequency
converter in hand-on mode, select [0] Disabled.
[1] * Enabled [Hand On] is enabled.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled To avoid unintended start of the frequency
converter from the LCP, select [0] Disabled.
[1] * Enabled [Auto On] is enabled.
0-44 [O/Reset] Key on LCP
Option: Function:
[0] Disabled Disable the o/reset key.
[1] * Enabled Enable both o and reset functions.
[7] Enable Reset
Only
Enable the reset function, and disable the
o function to avoid unintended stop of
the frequency converter.
3.1.5 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option: Function:
[0] * No copy
[1] All to LCP Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes, copy all
parameters to the LCP after commissioning.
[2] All from
LCP
Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3] Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. The latter
selection can be used to program several
frequency converters with the same function
without disturbing motor data that is already
set.
[10] Delete LCP
copy data
Delete copied parameters in LCP. This function
requires that LCP version is greater than or
equal to V11.00.
0-51 Set-up Copy
Option: Function:
[0] * No copy No function.
[1] Copy from
setup 1
Copy from set-up 1 to set-up 2.
[2] Copy from
setup 2
Copy from set-up 2 to set-up 1.
[9] Copy from
Factory setup
Copy factory setting to programming set-
up (selected in parameter 0-11 Programming
Set-up).
3.1.6 0-6* Password
0-60 Main Menu Password
Range: Function:
0* [0 - 999 ] Dene the password for access to the Main Menu
via the [Main Menu] key. Setting the value to 0
disables the password function. This parameter
hides after a password is dened.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access Disable the password dened in
parameter 0-60 Main Menu Password.
[1] LCP: Read only Prevent unauthorized editing of Main Menu
parameters.
[2] LCP: No access Prevent unauthorized viewing and editing
of Main Menu parameters.
Parameters Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 29
3 3