EasyManuals Logo

Danfoss VLT HVAC Basic Drive FC 101 Programming Guide

Danfoss VLT HVAC Basic Drive FC 101
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
5-13 Terminal 29 Digital Input
Parameter for conguring the input function on input terminal
29.
Option: Function:
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
[120] Lead Pump Start
[121] Lead Pump Alternation
[130] Pump 1 Interlock
[131] Pump 2 Interlock
[132] Pump 3 Interlock
[133] Pump 4 Interlock
[134] Pump 5 Interlock
3.6.3 5-3* Digital Outputs
Parameters for conguring the output functions for the
output terminals.
5-34 On Delay, Digital Output
Range: Function:
0.01 s* [0 - 600 s] Enter the delay time before the digital
output is switched on. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
5-35 O Delay, Digital Output
Range: Function:
0.01 s* [0 - 600 s] Enter the delay time before the digital
output is switched o. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
3.6.4 5-4* Relays
Parameters for conguring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[0] No operation
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[1] Control Ready The control board receives supply
voltage.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready/
remote control
The frequency converter is ready for
operation in auto-on mode.
[4] Standby / no
warning
The frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5] Drive running The motor runs.
[6] Running / no
warning
The motor runs, and no warnings are
present.
[7] Run in
range/no
warning
The motor runs within the programmed
current ranges, see
parameter 4-50 Warning Current Low and
parameter 4-51 Warning Current High. No
warnings are present.
[8] Run on ref/no
warning
The motor runs at reference speed and
with no warnings.
[9] Alarm An alarm activates output.
[10] Alarm or
warning
An alarm or warning activates output.
[12] Out of current
range
The motor current is outside the ranges
set in parameter 4-50 Warning Current
Low and parameter 4-51 Warning Current
High.
[13] Below current,
low
The motor current is lower than the limit
set in parameter 4-50 Warning Current
Low.
[14] Above current,
high
The motor current is higher than the
limit set in parameter 4-51 Warning
Current High.
[16] Below speed,
low
The frequency converter output speed is
lower than the limit set in
parameter 4-40 Warning Freq. Low.
[17] Above speed,
high
The frequency converter output speed is
higher than the limit set in
parameter 4-41 Warning Freq. High.
[19] Below
feedback, low
The feedback is lower than the limit set
in parameter 4-56 Warning Feedback Low.
Parameters Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 51
3 3

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals