EasyManuals Logo

Danfoss VLT HVAC Basic Drive FC 101 Programming Guide

Danfoss VLT HVAC Basic Drive FC 101
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[20] Above
feedback, high
The feedback is higher than the limit set
in parameter 4-57 Warning Feedback
High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in motor,
frequency converter, or thermistor.
[22] Ready, no
thermal
warning
The frequency converter is ready for
operation and no thermal warning is
present.
[23] Remote, ready,
no thermal
warning
The frequency converter is ready for
operation in auto mode, and no thermal
warning is present.
[24] Ready, Voltage
OK
The frequency converter is ready for
operation and mains voltage is within
the specied voltage range.
[25] Reverse The motor runs/is ready to run clockwise
when logic = 0 and counterclockwise
when logic = 1. Output changes as soon
as reversing signal is applied.
[26] Bus OK Active communication (no timeout) via
serial communication port.
[35] External
Interlock
See digital input.
[36] Control word
bit 11
Bit 11 in control word controls the relay.
[37] Control word
bit 12
Bit 12 in control word controls the relay.
[41] Below
reference, low
The reference is lower than the limit set
in parameter 4-54 Warning Reference Low.
[42] Above ref, high The reference is higher than the limit set
in parameter 4-55 Warning Reference
High.
[45] Bus Control The output is congured in
parameter 5-90 Digital & Relay Bus
Control.
[60] Comparator 0 See parameter group 13-1* Comparators.
If comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61] Comparator 1 See parameter group 13-1* Comparators.
If comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[62] Comparator 2 See parameter group 13-1* Comparators.
If comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63] Comparator 3 See parameter group 13-1* Comparators.
If comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1* Comparators.
If comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1* Comparators.
If comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70] Logic rule 0 See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[71] Logic rule 1 See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[72] Logic rule 2 See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[73] Logic rule 3 See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[74] Logic rule 4 See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[75] Logic rule 5 See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[80] SL digital
output A
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [38] Set dig. out. A high is
executed. The input goes low whenever
the smart logic [32] Action Set dig. out. A
low is executed.
[81] SL digital
output B
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [39] Set dig. out. B high is
executed. The input goes low whenever
the smart logic [33] Action Set dig. out. B
low is executed.
Parameters
VLT
®
HVAC Basic Drive FC 101
52 Danfoss A/S © 04/2018 All rights reserved. MG18B502
33

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals