EasyManuals Logo

Danfoss VLT HVAC Basic Drive FC 101 Programming Guide

Danfoss VLT HVAC Basic Drive FC 101
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[82] SL digital
output C
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [40] Set dig. out. C high is
executed. The input goes low whenever
the smart logic [34] Action Set dig. out. C
low is executed.
[83] SL digital
output D
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic [41] Action Set dig. out. D high is
executed. The input goes low whenever
the smart logic [35] Action Set dig. out. D
low is executed.
[160] No alarm The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
running and reverse).
[165] Local ref.
active
The output is high when local reference
is activated by the [Hand On] key on the
LCP or by hand-on command of digital
input.
[166] Remote ref.
active
The output is high when remote
reference is activated by the [Auto On]
key on the LCP or by auto-on command
of digital input.
[167] Start
command
activ
The output is high when there is an
active start command (that is, via digital
input bus connection or [Hand On] or
[Auto On], and no stop command is
active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in hand On mode (as
indicated by the LED light above [Hand
On]).
[169] Drive in auto
mode
The output is high when the frequency
converter is in auto On mode (as
indicated by the LED light above [Auto
On]).
[190] No-Flow A no-ow condition has been detected.
See parameter group 22-2* No-Flow
Detection.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to dene the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[193] Sleep Mode The frequency converter/system has
entered sleep mode. See parameter
group 22-4* Sleep Mode.
[194] Broken Belt
Function
A broken-belt condition has been
detected. Enable the function in
parameter 22-60 Broken Belt Function.
[196] Fire Mode The frequency converter is operating in
re mode. See parameter group 24-0*
Fire Mode.
[198] Drive Bypass To be used as a signal for activating an
external electromechanical bypass,
switching the motor directly on line.
See parameter group 24-1* Drive Bypass.
[211] Cascade Pump
1
[212] Cascade Pump
2
[213] Cascade Pump
3
[214] Cascade Pump
4
[215] Cascade Pump
5
5-41 On Delay, Relay
Array [2]
Range: Function:
0.01 s* [0.01 -
600 s]
Enter the delay of the relay cut-in time.
Select 1 of 2 internal mechanical relays in
an array function. See
parameter 5-40 Function Relay for details.
Parameters Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 53
3 3

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals