Start
term.18
1=on
0=off
Shaft speed
Start delay time
on
off
Brake delay time
Time
Output current
Relay 01
Pre-magnetizing
current or
DC hold current
Reaction time EMK brake
Par 2-20
Release brake current
Par 1-76 Start current/
Par 2-00 DC hold current
Par 1-74
Start speed
Par 2-21
Activate brake
speed
Mechanical brake
locked
Mechanical brake
free
Par 1-71
Par 2-23
e30ba074.13
Illustration 45: Mechanical Braking
Parameter 2-20 Release Brake Current
Table 168: Parameter 2-20 Release Brake Current
2-20 Release Brake Current
Default value: Size related
Parameter type: Range, 10 - par. 16-37 A
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Set the motor current for release of the mechanical braking when a start condition is present. The default value is the maximum
current the inverter can provide for the particular power size. The upper limit is specified in parameter 16-37 Inv. Max. Current.
N O T I C E
When mechanical brake control output is selected, but no mechanical braking is connected, the function does not work by de-
fault setting due to too low motor current.
Parameter 2-21 Activate Brake Speed [RPM]
Table 169: Parameter 2-21 Activate Brake Speed [RPM]
2-21 Activate Brake Speed [RPM]
Default value: Size related
Parameter type: Range, 0 - par. 4-53 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Set the motor speed for activation of the mechanical braking when a stop condition is present.
AU275636650261en-000101 / 130R0334 | 119Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control

Related product manuals