Option
Name
Description
[0]*
Do not reset
[1]
Reset counter
To reset the running hours counter to 0, select [1] Reset and press [OK] (see parameter 15-01 Running
Hours). This parameter cannot be selected via the serial port, RS485. Select [0] Do not reset if no reset of
the running-hours counter is required.
5.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data sources (parameter 15-10 Logging Source) at individual rates (parameter
15-11 Logging Interval). A trigger event (parameter 15-12 Trigger Event) and window (parameter 15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
Parameter 15-10 Logging Source
Table 769: Parameter 15-10 Logging Source
15-10 Logging Source
Default value: [0] None
Parameter type: Option, Array [4]
Setup: 2 setups
Conversion index: -
Data type: Uint16
Change during operation: True
Select the variables to be logged.
Option
Name
Description
[0]*
None
[15]
Readout: Actual setup
[1397]
Alert alarm word
[1398]
Alert warning word
[1399]
Alert status word
[1472]
Legacy alarm word
[1473]
Legacy warning word
[1474]
Leg. ext. status word
[1600]
Control word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status word
[1606]
Actual position
[1607]
Target position
This option is only available with software version 48.XX.
[1608]
Position error
This option is only available with software version 48.XX.
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor voltage
[1613]
Frequency
[1614]
Motor current
AU275636650261en-000101 / 130R0334 | 479Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control