Parameter 33-88 Status Word at Alarm
Table 1234: Parameter 33-88 Status Word at Alarm
33-88 Status Word at Alarm
Default value: 0
Parameter type: Range, 0 - 65535
Setup: 2 setups
Conversion index: 0
Data type: Uint16
Change during operation: True
5.26.6 33-9* MCO Port Settings
Parameter 33-90 X62 MCO CAN node ID
Table 1235: Parameter 33-90 X62 MCO CAN node ID
33-90 X62 MCO CAN node ID
Default value: 127
Parameter type: Range, 0 - 127
Setup: 2 setups
Conversion index: 0
Data type: Uint8
Change during operation: True
Parameter 33-91 X62 MCO CAN Baud Rate
Table 1236: Parameter 33-91 X62 MCO CAN Baud Rate
33-91 X62 MCO CAN Baud Rate
Default value: [20] 125 Kbps
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Option
Name
Description
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]*
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
[24]
1000 Kbps
Parameter 33-94 X60 MCO RS485 Serial Termination
Table 1237: Parameter 33-94 X60 MCO RS485 Serial Termination
33-94 X60 MCO RS485 Serial Termination
Default value: [0] Off
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Off
[1]
On
AU275636650261en-000101 / 130R0334 | 623Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control