5.31.4 42-3* General
Parameter 42-30 External Failure Reaction
Table 1385: Parameter 42-30 External Failure Reaction
42-30 External Failure Reaction
Default value: [0] STO
Parameter type: Option
Setup: 1 setup
Conversion index: -
Data type: Uint8
Change during operation: False
Option
Name
Description
[0]*
STO
[1]
SS1-a
[2]
SS1-b
Parameter 42-31 Reset Source
Table 1386: Parameter 42-31 Reset Source
42-31 Reset Source
Default value: [0] Drive reset
Parameter type: Option
Setup: 1 setup
Conversion index: -
Data type: Uint8
Change during operation: False
Option
Name
Description
[0]*
Drive reset
[1]
Drive safe reset
[2]
Safe option DI2_A
Parameter 42-33 Parameter Set Name
Table 1387: Parameter 42-33 Parameter Set Name
42-33 Parameter Set Name
Default value: Size related
Parameter type: Range, 0 - 8
Setup: 1 setup
Conversion index: 0
Data type: VisibleString
Change during operation: False
Name of the safe parameter set. It is recommended to enter text with characters to avoid bad customization data error.
AU275636650261en-000101 / 130R0334672 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V