Page #52 background imageLoading...
Page #52 background image
Option
Name
Description
[125]
ft
3
/s
[126]
ft
3
/min
[127]
ft
3
/h
[130]
lb/s
[131]
lb/min
[132]
lb/h
[140]
ft/s
[141]
ft/min
[145]
ft
[160]
°F
[170]
psi
[171]
lb/in
2
[172]
in WG
[173]
ft WG
[176]
kpsi
[177]
MPa
[178]
kBar
[180]
hp
Parameter 0-31 Min Value of User-defined Readout
Table 22: Parameter 0-31 Min Value of User-defined Readout
0-31 Min Value of User-defined Readout
Default value: 0 CustomReadoutUnit
Parameter type: Range, -999999.99 CustomReadoutUnit
- par. 0-32
Setup: All setups
Conversion index: -2
Data type: Int32
Change during operation: True
This parameter sets the minimum value of the custom-defined readout (occurs at 0 speed). Only possible to set different from 0
when selecting a linear unit in parameter 0-30 Unit for User-defined Readout. For quadratic and cubic units, the minimum value is 0.
Parameter 0-32 Max Value of User-defined Readout
Table 23: Parameter 0-32 Max Value of User-defined Readout
0-32 Max Value of User-defined Readout
Default value: 100 CustomReadoutUnit
Parameter type: Range, par. 0-31 -999999.99 Custom-
ReadoutUnit
Setup: All setups
Conversion index: -2
Data type: Int32
Change during operation: True
This parameter sets the maximum value to be shown when the speed of the motor has reached the set value for parameter 4-13
Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz] (depends on setting in parameter 0-02 Motor Speed Unit).
AU275636650261en-000101 / 130R033452 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control