Parameter 0-42 [Auto On] Key on LCP
Table 30: Parameter 0-42 [Auto On] Key on LCP
0-42 [Auto On] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]
Disabled
Avoids accidental stop of the drive in auto-on mode.
[1]*
Enabled
[2]
Password
Avoids unauthorized start in auto-on mode. If parameter 0-42 [Auto on] Key on LCP is included in the Quick
Menu, then define the password in parameter 0-65 Personal Menu Password.
Parameter 0-43 [Reset] Key on LCP
Table 31: Parameter 0-43 [Reset] Key on LCP
0-43 [Reset] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]
Disabled
No effect when [Reset] is pressed. Avoids accidental alarm reset.
[1]
Enabled
[2]
Password
Avoids unauthorized start in auto-on mode. If parameter 0-43 [Reset] Key on LCP is included in
the Quick Menu, then define the password in parameter 0-65 Personal Menu Password.
[7]
Enabled without OFF
Resets the drive without setting it in Off mode.
[8]
Password without
OFF
Resets the drive without setting it in Off mode. A password is required when pressing [Reset]
(see option [2] Password).
Parameter 0-44 [Off/Reset] Key on LCP
Table 32: Parameter 0-44 [Off/Reset] Key on LCP
0-44 [Off/Reset] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Enable or disable the [Off/Reset] key.
Option
Name
Description
[0]
Disabled
[1]*
Enabled
[2]
Password
AU275636650261en-000101 / 130R0334 | 55Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control