Troubleshooting
Remove the power to the drive and remove the brake resistor.
7.2.26 WARNING/ALARM 28, Brake Check Failed
Cause
The brake resistor is not connected or not working.
Troubleshooting
Check parameter 2-15 Brake Check.
7.2.27 ALARM 29, Heat Sink Temp
Cause
The maximum temperature of the heat sink is exceeded. The temperature fault is not reset until the temperature drops below a
defined heat sink temperature. The trip and reset points are different based on the drive power size.
Troubleshooting
Check for the following conditions:
The ambient temperature is too high.
The motor cables are too long.
Incorrect airflow clearance above and below the drive.
Blocked airflow around the drive.
Damaged heat sink fan.
Dirty heat sink.
7.2.28 ALARM 30, Motor Phase U Missing
Cause
Motor phase U between the drive and the motor is missing.
Troubleshooting
W A R N I N G
HAZARDOUS VOLTAGE
AC drives contain hazardous voltage when connected to AC mains or connected on the DC terminals. Failure to perform installa-
tion, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
Disconnect power before proceeding.
Remove the power from the drive and check motor phase U.
7.2.29 ALARM 31, Motor Phase V Missing
Cause
Motor phase V between the drive and the motor is missing.
Troubleshooting
W A R N I N G
HAZARDOUS VOLTAGE
AC drives contain hazardous voltage when connected to AC mains or connected on the DC terminals. Failure to perform installa-
tion, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
Disconnect power before proceeding.
Remove the power from the drive and check motor phase V.
7.2.30 ALARM 32, Motor Phase W Missing
Cause
Motor phase W between the drive and the motor is missing.
AU275636650261en-000101 / 130R0334 | 705Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT HVAC Drive FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive FC 102 and is the answer not in the manual?

Danfoss VLT HVAC Drive FC 102 Specifications

General IconGeneral
EnclosureIP20, IP21, IP55
Ambient Temperature Range-10°C to +40°C
Storage Temperature Range-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Communication ProtocolsModbus RTU, BACnet, Profibus
CertificationsCE, UL, cUL
Control PrinciplePWM
Cooling MethodForced air cooling
Input Voltage200-240V, 380-480V, 525-600V
Control Modessensorless vector control, closed loop vector control