What to do if the Danfoss VLT MCD 600 Controller shows an instant overcurrent error?
- KKimberly CooperAug 25, 2025
If the Danfoss Controller displays an instant overcurrent error, it means the current on all three phases has exceeded 7.2 times the value set for the motor's full load current. This could be due to a locked rotor or an electrical fault in the motor or cabling. Check for jammed loads and inspect the motor and cables for faults.