Parameter group number
Parameter group name
Default setting
5-5
Overcurrent
400%
5-6
Overcurrent Delay
00:00 (mm:ss)
5-7
Undervoltage
350 V
5-8
Undervoltage Delay
00:01 (mm:ss)
5-9
Overvoltage
500 V
5-10
Overvoltage Delay
00:01 (mm:ss)
5-11
Underpower
10%
5-12
Underpower Delay
00:01 (mm:ss)
5-13
Overpower
150%
5-14
Overpower Delay
00:01 (mm:ss)
5-15
Excess Start Time
00:20 (mm:ss)
5-16
Restart Delay
00:10 (mm:ss)
5-17
Starts per Hour
0
5-18
Phase Sequence
Any Sequence
6
Protection Actions
6-1
Auto-Reset Count
0
6-2
Auto-Reset Delay
00:05 (mm:ss)
6-3
Current Imbalance
Soft Trip and Log
6-4
Undercurrent
Soft Trip and Log
6-5
Overcurrent
Soft Trip and Log
6-6
Undervoltage
Soft Trip and Log
6-7
Overvoltage
Soft Trip and Log
6-8
Underpower
Log Only
6-9
Overpower
Log Only
6-10
Excess Start Time
Soft Trip and Log
6-11
Input A Trip
Soft Trip and Log
6-12
Input B Trip
Soft Trip and Log
6-13
Network Communications
Soft Trip and Log
6-14
Remote Keypad Fault
Soft Trp and Log
6-15
Frequency
Soft Trip and Log
6-16
Phase Sequence
Soft Trip and Log
6-17
Motor Overtemperature
Soft Trip and Log
AQ262141844215en-000401 / 175R1174 | 77Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide