Table 59: 3-5 - Initial Current-2
Range
Function
*200%
100–600%
FLC
Sets the initial start current level for current ramp starting as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated. If current ramp starting is not re-
quired, set the initial current equal to the current limit.
Table 60: 3-6 - Current Limit-2
Range
Function
*350%
100–
600%
FLC
Sets the current limit for constant current and current ramp soft starting as a percentage of motor full load
current.
N O T I C E
The VLT® Soft Starter MCD 600 applies the current limit on all soft starts, including adaptive control. If the
current limit is too low or the start ramp time (parameter 2-2 Start Ramp Time) is too short, the motor may
not start successfully.
Table 61: 3-7 - Adaptive Start Profile-2
Option
Function
Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft start.
Early Acceleration
*
Constant Acceleration
Late Acceleration
Table 62: 3-8 - Kickstart Time-2
Range
Function
* 0000 ms
0–2000 ms
Sets the kickstart duration.
A setting of 0 disables kickstart.
Table 63: 3-9 - Kickstart Level-2
Range
Function
*500%
100–700% FLC
Sets the level of the kickstart current.
Table 64: 3-10 - Jog Torque-2
Range
Function
*50%
20–100%
Sets the current limit for jog operation.
Table 65: 3-11 - Stop Mode-2
Option
Function
Selects the stop mode.
Coast To Stop
*
TVR Soft Stop
Adaptive Control
AQ262141844215en-000401 / 175R1174 | 87Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals