Table 59: 3-5 - Initial Current-2
Sets the initial start current level for current ramp starting as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated. If current ramp starting is not re-
quired, set the initial current equal to the current limit.
Table 60: 3-6 - Current Limit-2
Sets the current limit for constant current and current ramp soft starting as a percentage of motor full load
current.
N O T I C E
The VLT® Soft Starter MCD 600 applies the current limit on all soft starts, including adaptive control. If the
current limit is too low or the start ramp time (parameter 2-2 Start Ramp Time) is too short, the motor may
not start successfully.
Table 61: 3-7 - Adaptive Start Profile-2
Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft start.
Table 62: 3-8 - Kickstart Time-2
Sets the kickstart duration.
A setting of 0 disables kickstart.
Table 63: 3-9 - Kickstart Level-2
Sets the level of the kickstart current.
Table 64: 3-10 - Jog Torque-2
Sets the current limit for jog operation.
Table 65: 3-11 - Stop Mode-2