1-52 Min. Speed Normal Magnetizing [Hz]
Range: Function:
Use this parameter along with 1-50 Motor
Magnetizing at Zero Speed.
0.0 Hz* [0.0-10.0 Hz] Set frequency required for normal
magnetizing current. If frequency is set
lower than motor slip frequency, 1-50
Motor Magnetizing at Zero Speed is
inactive.
Magn. current
130BD016.10
Hz
Par.1-50
Par.1-51
100%
Par.1-52 RPM
Illustration 4.2
1-55 U/f Characteristic - U
Range: Function:
This parameter is an array parameter [0-5]
and is only functional when 1-01 Motor
Control Principle is set to [0] U/f.
0.0 V* [0.0-999.9 V] Enter voltage at each frequency point to
manually form a U/f characteristic
matching motor. Frequency points are
defined in 1-56 U/f characteristics - F.
1-56 U/f Characteristic - F
Range: Function:
This parameter is an array parameter [0-5]
and is only functional when 1-01 Motor
Control Principle is set to [0] U/f.
0.0
Hz*
[0.0-1000.0
Hz]
Enter frequency points to manually form a
U/f characteristic matching motor. Voltage
at each point is defined in 1-55 U/f
Characteristic - U.
Make a U/f characteristic based on 6
definable voltages and frequencies, see
Illustration 4.3.
Simplify U/f characteristics by merging 2
or more points (voltages and frequencies),
respectively, are set equal.
Motor Voltage
Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1]
1-55[0]
1-56
[0]
1-56
[1]
1-56
[2]
1-56
[3]
1-56
[4]
1-56
[5]
130BD017.10
Illustration 4.3 U/f Characteristics
NOTE
For 1-56 U/f characteristics - F the following applies
[0] [1] [2] [3] [4] [5]
4.2.4 1-6* Load Dependent Setting
Parameters for adjusting the load-dependent motor
settings.
1-60 Low Speed Load Compensation
Range: Function:
Use this parameter to gain optimum U/f
characteristic when running at low speed.
100 %* [0-199 %] Enter percentage in relation to load when
motor runs at low speed.
Change-over point is automatically
calculated based on motor size.
130BD018.10
60%
0%
100%
U
m
Changeover
f
out
Par.1-60 Par.1-61
Illustration 4.4
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
16 MG02C602 - VLT
®
is a registered Danfoss trademark
44

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals