14-22 Operation Mode
Option: Function:
14-22 Operation Mode also reverts to default
setting [0] Normal Operation.
14-26 Action at Inverter Fault
Option: Function:
[0] Trip When the frequency converter detects an over-
voltage, it will trip immediately.
NOTE
It is recommended to choose [0] Trip in
hoisting applications.
[1] * Warning When the frequency converter detects an over-
voltage, it will give warning immediately. After
protection filter, it will trip.
NOTE
It is recommended to disable protection
mode in hoisting applications.
4.11.4 15-4* Drive Identification
Parameters containing read only information about the
hardware and software configuration of the frequency
converter.
14-41 AEO Minimum Magnetization
Range: Function:
66%* [40-75%] Enter the minimum allowable magnetization
for AEO. Selecting a low value reduces energy
loss in the motor, but may also reduce
resistance to sudden load changes.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
46 MG02C602 - VLT
®
is a registered Danfoss trademark
44

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals