0-50 LCP Copy
Option: Function:
[0] * No copy No function.
[1] All to LCP Copies all parameters in all set-ups from the
frequency converter memory to the LCP. For
service purposes, copy all parameters to the
LCP after commissioning.
[2] All from
LCP
Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3] Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. This selection
can be used to program several frequency
converters with the same function without
disturbing motor data that is already set.
0-51 Set-up Copy
Use this parameter to copy parameters between set-ups.
Option: Function:
[0] * No copy
[1] Copy from setup 1
[2] Copy from setup 2
[3] Copy from setup 3
[4] Copy from setup 4
[9] Copy from Factory setup
Parameter Descriptions
VLT
®
Midi Drive FC 280
30 Danfoss A/S © 12/2015 All rights reserved. MG07C102
44

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals