EasyManuals Logo

Danfoss VLT Midi Drive FC 280 Programming Guide

Danfoss VLT Midi Drive FC 280
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
[36] Control word
bit 11
[37] Control word
bit 12
[40] Out of ref
range
This option is active when the actual
speed is outside the settings in
parameter 4-52 Warning Speed Low to
parameter 4-55 Warning Reference High.
[41] Below
reference low
This option is active when the actual
speed is below the speed reference
setting.
[42] Above
reference high
This option is active when the actual
speed is above the speed reference
setting.
[45] Bus Ctrl Controls output via eldbus. The state of
the output is set in parameter 5-90 Digital
& Relay Bus Control. The output state is
retained in the event of eldbus timeout.
[46] Bus Ctrl On at
timeout
Controls output via eldbus. The state of
the output is set in parameter 5-90 Digital
& Relay Bus Control. When bus timeout
occurs, the output state is set high (On).
[55] Pulse output
[56] Heat sink
cleaning
warning, high
[60] Comparator 0 See parameter group 13-1* Comparators.
If comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61] Comparator 1 See parameter group 13-1* Comparators.
If comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62] Comparator 2 See parameter group 13-1* Comparators.
If comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63] Comparator 3 See parameter group 13-1* Comparators.
If comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1* Comparators.
If comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1* Comparators.
If comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic Rule 0 See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71] Logic Rule 1 See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72] Logic Rule 2 See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73] Logic Rule 3 See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic Rule 4 See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic Rule 5 See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL Digital
Output A
See parameter 13-52 SL Controller Action.
The output goes high whenever the
smart logic action [38] Set dig. out. A high
is executed. The output goes low
whenever the smart logic action [32] Set
dig. out. A low is executed.
[81] SL Digital
Output B
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [39] Set dig. out. B high is
executed. The input goes low whenever
the smart logic action [33] Set dig. out. B
low is executed.
[82] SL Digital
Output C
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [40] Set dig. out. C high is
executed. The input goes low whenever
the smart logic action [34] Set dig. out. C
low is executed.
[83] SL Digital
Output D
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [41] Set dig. out. D high is
executed. The input goes low whenever
the smart logic action [35] Set dig. out. D
low is executed.
[160] No alarm The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
Running AND Reverse).
[165] Local reference
active
[166] Remote ref
active
[167] Start command
active
The output is high when there is an
active start command, and no stop
command is active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in hand-on mode.
[169] Drive in auto
mode
The output is high when the frequency
converter is in auto-on mode.
[170] Homing
Completed
The homing operation is completed. This
option is only eective when
parameter 37-00 Application Mode is set to
[2] Position Control.
[171] Target Position
Reached
The target position is reached. This option
is only eective when
parameter 37-00 Application Mode is set to
[2] Position Control.
[172] Position
Control Fault
A fault occurred in the positioning
process. Refer to parameter 37-18 Pos. Ctrl
Parameter Descriptions Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 55
4 4

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals