REV 8/03
10
EXIT THE MENU - Press Select
button twice to exit to the normal operation
Otherwise press Menu button to advance to the
next menu
12-PASSWORD B
Press Select button to enter password.
PASSWORD B: OO
Default password is 00
Press Select button to cycle the password from
00 to 99. After entering the password, press
Menu button to advance to menu 13. if an
incorrect password is entered, panel will display
“ BAD PASSWORD” for one minute and
automatically exit. See the Procedure To
Retrieve Password On MINI-DAP II above.
Otherwise panel will advance to the next menu
Press Menu button to advance to the next menu
13-DAY SCHEDULE
Press Select button to display the current setting
DAY SCHEDULE: Y
Y (Yes) or N (No)
Press Select button to change the setting to NO
The time-of-day schedule can be turned
on and off at this menu. When this
menu is set to Y (YES), the Mini-DAP
operates according to the time-of-day
schedule specified in Menus 20 through
26. If this menu is set to N (NO), the
Mini-DAP does not follow a schedule. It
operates continuously in the normal
mode.
NOTE: All the day schedule menus ( 14
to 26) below will not show if Menu #13 is
set for “N”.
Press Menu button to advance to the next menu
14-OVERRIDE ENBL.
Press Select button to display the current setting
OVERRIDE ENBL: Y
Y (Yes) or N (No)
Press Select button to change the setting to NO
This menu enables and disables user
requests to override the time-of-day
schedule and force the Mini-DAP into
“occupied” mode. If this menu is set to
Y (YES), the “Menu 2-OVERRIDE
RQST” appears to allow override
requests. If this menu is set to N (NO),
then “Menu 2 OVERRIDE RQST” never
appears and override requests are
inoperable.
Press Menu button to advance to the next menu
15-OVERRIDE TIME
Press Select button to display the current setting
OVERRIDE HRS: 1
1 to 12 hours
Press Select button to change the Hour
This menu specifies the duration of each
override request made using “Menu 2-
OVERRIDE RQST”.
Press Menu button to advance to the next menu
16-SETUP COOL
Press Select
button to display the current setting
SETUP COOL: 5 0 to 30°F
Press Select button to change the temperature
range from 1°F to 30°F. Default value is 5°F
When a SETBACK/UP time-of-day
schedule is in effect and the Mini-DAP is
operating in the “unoccupied” mode, the
effective cooling setpoint will be
adjusted upward
by the amount
specified in this menu.
Press Menu button to advance to the next menu
17-SETBACK HEAT
Press Select button to display the current setting
SETBACK HEAT: 5 0 to 30° F
Press Select button to change the temperature
range from 1°F to 30°F. Default value is 5°F
When a SETBACK/UP time-of-day
schedule is in effect and the Mini-DAP is
operating in the “unoccupied” mode, the
effective heating setpoint will be
adjusted downward
by the amount
specified in this menu.
Press Menu button to advance to the next menu
18-SETUP DEHUM
Press Select button to display the current setting
SETUP DEHUM: 5 0 to 30% RH
Press Select button to change the humidity
range from 1 % to 30 %. Default value is 5 %
When a SETBACK/UP time-of-day
schedule is in effect and the Mini-DAP II
is operating in the “unoccupied” mode,
the effective setpoint for
dehumidification will be adjusted upward
by the amount specified in the menu.
Press Menu button to advance to the next menu
19-SETBACK HUMID
Press Select button to display the current setting
SETBACK HUMID: 5 0 to 30% RH
Press Select button to change the humidity
range from 1 % to 30 %. Default value is 5 %
When a SETBACK/UP time-of-day
schedule is in effect and the Mini-DAP is
operating in the “unoccupied” mode, the
effective setpoint for humidification will
be adjusted downward
by the amount
specified in the menu.