DT9502
40 20171205-V3
7.7. The temperature value belonging to the 4 mA value
(05
menu item)
Function The apparatus regulates the loop current between 4 and 20
mA in proportion with the measured temperature.
In this menu item any °C values between -200.0 °C and
600.0 °C could be assigned to the 4 mA loop current.
[Factory default setting: -200.0 °C]
Attention! In addition to selecting the temperature value
assigned to 4 mA, also the temperature value to be
assigned to 20 mA must be selected (The next menu item).
Sequence of operations 1. Enter the menu with the supervisor code.
Read chapter 7.1. Writing the code in to see how the code
should be written in. On the display you see this:
.
2. Keep stepping with the button as long as you see this
menu item:
.
3. Enter the menu item by using the ENTER button.
4. The number
 is visible on the display. Digit 2 is
blinking. The blinking digit indicates which of the digits is
selected. The selection can be modified by using the
button.
6. Using the button you can go to the next digit.
7. By using the button, you can increase the value of the
blinking digit:
,,,,,,,,,, etc.
8. If you have selected the last digit (the digit on the right
side), and you press the button, a blinking colon will
appear on the left side:
. This colon indicates,
that the positive or negative sign is being selected, and you
can now change it by the button.
9. With the
button you can switch the negative sign on or
off.
 = 200.0 °C
 = -200.0 °C