EasyManua.ls Logo

DEEP SEA ELECTRONICS DSE8620 - Rs485 Serial Port

DEEP SEA ELECTRONICS DSE8620
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DSE Model 8620 AMF Controller Operators Manual
63
5.2.1 RS485 SERIAL PORT
This section is included to give information about the currently selected serial port and external modem
(if connected).
The items displayed on this page will change depending upon configuration of the module. You are
referred to your system supplier for further details.
NOTE:- Factory Default settings are for the RS485 port to operating at 19200 baud,
modbus slave address 10.
Module RS485 port configured for connection to a modbus master.
DSE86xx series modules operate as a modbus RTU slave device.
In a modbus system, there can be only one Master, typically a PLC, HMI
system or PC SCADA system.
This master requests for information from the modbus slave (DSE86xx
series module) and may (in control systems) also send request to change operating modes etc. Unless
the Master makes a request, the slave is quiet’ on the data link.
The factory settings are for the module to communicate at 19200 baud, modbus slave address 10.
To use the RS485 port, ensure that port usage’ is correctly set using the DSE Configuration Suite
Software.
Required settings are shown below.
‘Master inactivity timeout should be set to at least twice the value of the system scan time. For
example if a modbus master PLC requests data from the DSE86xx modbus slave once per second, the
timeout should be set to at least 2 seconds.
The DSE Modbus Gencomm document containing register mappings inside the DSE module is
available upon request from support@deepseaplc.com. Email your request along with the serial
number of your DSE module to ensure the correct information is sent to you.

Table of Contents

Related product manuals