MIB Installation Instructions and Reference Handbook
DEIF A/S
Page 30 of 50
Screen no. 8
Backlight on-time:
The on-time can be set from 0 to 120 minutes.
0 minutes = always “on”.
After the preset on-time has expired and none of
the keys have been touched, the backlight will
turn off automatically.
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next screen
Example: 2 minutes “on”
Screen no. 9
Total sliding windows time of demand:
Total sliding windows time of demand is from:
1-30 minutes.
The window slides constantly once every minute.
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next screen
Example: Total sliding windows time: 8 minutes
Screen no. 10
Reset of max. and min.:
and to change between yes and no
to accept changes and move to next screen
Example: Yes to reset both max. and min.
Screen no. 11
Lock/unlock reset function of saved energy:
Enable to reset energy data saved in MIB.
1 = enable (possible to reset counters)
0 = disable (impossible to reset counters)
and to change between 1 and 0
to accept changes and move to next screen
Example: Enable