Dell PowerEdge R6625 - Installing the Intrusion Switch Module

Dell PowerEdge R6625
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Follow the procedure listed in the Before working inside your system.
3. Remove the expansion card riser.
NOTE: Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
Steps
1. Disconnect the intrusion switch cable from the connector on the rear I/O board.
2. Using a Phillips #1 screwdriver, loosen the screw on the intrusion switch module.
3. Slide the intrusion switch module out of the slot on the system.
NOTE: The numbers on the image do not depict the exact steps. The numbers are for representation of sequence.
Figure 154. Removing the intrusion switch module
Next steps
1. Replace the intrusion switch module.
Installing the intrusion switch module
Prerequisites
1. Follow the safety guidelines listed in the Safety instructions.
2. Follow the procedure listed in Before working inside your system.
3. Remove the expansion card riser.
NOTE:
Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
Steps
1. Align and slide the intrusion switch module into the slot in the system until firmly seated.
Installing and removing system components
169