Local Outputs Tab
Page 27 of 67
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
Local Outputs Tab
Outputs 1 to 4 on the eZV-440 controller are physical Universal Outputs. Outputs 5 and 6 are
used by the actuator connector (1 Universal Output, 1 TRIAC Output). This section describes how
to set up these physical outputs on the Local Outputs tab in this configuration graphic.
The Universal Outputs are reconfigured as these outputs depending on the object being
controlled:
Analog 0-10VDC output, 5mA maximum
24 VAC TRIAC output, 0.5 A maximum
The output options for the eZV-440 configurable model are listed here:
Electric Duct
Exhaust Fan
Electric Baseboard
Occupancy Indicator
Hydronic Duct
GCL-controlled AO*
Hydronic Baseboard
GCL-controller BO*
VAV/VVT Damper
Series Fan (single duct VAV only)
*Available only with eZVP-440 programmable models
Parallel Fan (single duct VAV only)