Appendix A: Database Configuration Objects
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
WindowContact MV6 N/A
open windows in order to
control local heating or
NotUsed_, Closed_, Open_.
Button 1 to 8
MV1010
to
MV1017
N/A
Options for the buttons
of the LINKnet network
sensor used with the
eZV-440.
NotUsed_, EcoModeToggle_,
OccupancyOff_, OccupancyOn_,
OccupancyToggle_,TempUnitsToggle_,
TempDown_, TempUp_, TempSelect_,
FanDown_, FanUp_, FanCycle_,
FanSelect_, Info_.
Occupancy Configuration Objects
Also see these related sections in the document:
•
Set Up a Hardwired Occupancy Input
on page 23
•
Set Up a DNS-24L Network Sensor
on page 39
•
Occupancy Modes
on page 47
Local Schedule SCH1
Local schedule object on the
controller. It is used to provide local
scheduled operations based on a 7-
day recurring schedule. Exception
scheduling is not supported.
N/A
Remote Schedule MV1
An object that can be written over
the network to provide a remote
NotUsed_, Off_, On_.
OccOvrdButton MV2
Network sensor button used as an
occupancy override button.
NotUsed_, Off_, On_.
Default = NotUsed_
OccToggleButton MV3
Network sensor button to toggle
between standby and occupied
modes during scheduled occupancy
NotUsed_, Off_, On_.
OccMotion MV4
Motion sensor that is integrated into
the network sensor. Object can be
set up to be a maintained contact or
a momentary contact type.
NotUsed_, Off_, On_.
OccMaintainedContact MV5
Used for any maintained contact
signal type like a hotel keycard
holder, manual switch or
mechanical time clock input.
NotUsed_, Off_, On_.
OccupancyMode MV800 Occupancy modes
Unoccupied_Ovrd_,
Standby_, Balancing_,
Debug_.
OccIndicator MV806
Used to display the occupancy icon
on the network sensor LCD screen.
NotUsed_, Off_, On_.
Default = NotUsed_