Object Name
Object
Ref
Default
Units
Description
Options
WindowContact MV6 N/A
Window contact to detect
open windows in order to
control local heating or
cooling.
NotUsed_, Closed_, Open_.
Default = NotUsed_
Button 1 to 8
MV1010
to
MV1017
N/A
Options for the buttons
of the LINKnet network
sensor used with the
eZV-440.
NotUsed_, EcoModeToggle_,
OccupancyOff_, OccupancyOn_,
OccupancyToggle_,TempUnitsToggle_,
TempDown_, TempUp_, TempSelect_,
FanDown_, FanUp_, FanCycle_,
FanSelect_, Info_.
Default = NotUsed_
Occupancy Configuration Objects
Also see these related sections in the document:
Set Up a Hardwired Occupancy Input
on page 23
Set Up a DNS-24L Network Sensor
on page 39
Occupancy Modes
on page 47
Object Name
Object
Ref
Description
Options
Local Schedule SCH1
Local schedule object on the
controller. It is used to provide local
scheduled operations based on a 7-
day recurring schedule. Exception
scheduling is not supported.
N/A
Remote Schedule MV1
An object that can be written over
the network to provide a remote
schedule input.
NotUsed_, Off_, On_.
Default = NotUsed_
OccOvrdButton MV2
Network sensor button used as an
occupancy override button.
NotUsed_, Off_, On_.
Default = NotUsed_
OccToggleButton MV3
Network sensor button to toggle
between standby and occupied
modes during scheduled occupancy
periods.
NotUsed_, Off_, On_.
Default = NotUsed_
OccMotion MV4
Motion sensor that is integrated into
the network sensor. Object can be
set up to be a maintained contact or
a momentary contact type.
NotUsed_, Off_, On_.
Default = NotUsed_
OccMaintainedContact MV5
Used for any maintained contact
signal type like a hotel keycard
holder, manual switch or
mechanical time clock input.
NotUsed_, Off_, On_.
Default = NotUsed_
OccupancyMode MV800 Occupancy modes
Unoccupied_, Occupied_,
Unoccupied_Ovrd_,
Standby_, Balancing_,
Debug_.
Default = Unoccupied_
OccIndicator MV806
Used to display the occupancy icon
on the network sensor LCD screen.
NotUsed_, Off_, On_.
Default = NotUsed_

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Controls eZVP-440 and is the answer not in the manual?

Delta Controls eZVP-440 Specifications

General IconGeneral
BrandDelta Controls
ModeleZVP-440
CategoryController
LanguageEnglish

Related product manuals