Local Outputs Tab
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
Select this option if you are:
GCL-controlled AO* Creating a custom AO object.
None_, Custom1, Custom2
Default = None_
GCL-controlled BO* Creating a custom BO object.
None_, Custom1, Custom2
Default = None_
*Available only with eZVP-440 programmable model
The control sources listed in the
field will change depending on the
option that was selected in the
field.
For a list of output configuration software objects that correspond to the control
sources, see
Output Configuration Objects
on page 60.
2. In the
field, select the method of control used on the output device signal.
The control types available in the drop-down list will change depending on the option
that was selected in the
field and the physical output used to connect to the
output device. For more information about control types, see
Appendix B Control Types
on page
63.
ECM fans may require both an analog speed and a binary stop/start signal. For example,
for a modulating series fan sequence that has both an analog speed and binary
stop/start signal, this is how you should set it up:
3. In the
field, choose between direct or reverse control.
4. If you selected series or parallel fan in the
field, click the “+” sign at the end of
the row for additional settings:
•
Allows you to select the occupancy mode in which the fan
runs constantly. If you are setting up a parallel fan, select
.
In occupancy modes where the fan is not running constantly, the algorithm
assumes the fan is running intermittently.