EasyManuals Logo
Home>Delta Electronics>DC Drives>Network Device VFD-S

Delta Electronics Network Device VFD-S User Manual

Delta Electronics Network Device VFD-S
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
Chapter 7 Troubleshooting |VFD-S Series
7-4 Revision August 2008, SE09, SW V2.61
7.5 Over Heat (OH)
AC motor drive overheats
Heat sink overheats
Check if temperature of heat sink
is greater than 90
O
C
No
No
No
No
Ye s
Yes
Yes
Ye s
Ye s
Reduce load
No
Temperature detection malfunctions.
Please contact DELTA.
If cooling fan functions normally
Change cooling fan
Check if cooling fan is jammed
Remove obstruction
Check if surrounding temperature
is within specification
Adjust surrounding temperature
to specification
Maybe AC motor drive has malfunction or
misoperation due to noise. Please contact
DELTA.
Is load too large
7.6 Overload
OL1/ OL2
OL
Reduce load or increase the power of AC motor drive
Check for correct settings at
Pr. 06-06 and 06-07
Yes
Yes
No
No
Modify setting
Is load too large
Maybe AC motor drive has malfunction
or misoperation due to noise.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics Network Device VFD-S and is the answer not in the manual?

Delta Electronics Network Device VFD-S Specifications

General IconGeneral
BrandDelta Electronics
ModelNetwork Device VFD-S
CategoryDC Drives
LanguageEnglish

Related product manuals