Modbus TCP Remote I/O Communication Module RTU-EN01
DVP-PLC Operation Manual
26
1. Enable:
Decide whether to enable the counter in this column.
2. Count up/count down:
Decide whether the counter will be counting up or counting down.
3. Up bound/low bound:
The upper bound and lower bound of the counting. Range: -32,768 ~ 32,767.
4. Count source RX NO.:
No. of the external input point RX of the counting source. Range: RX#0 ~ RX#255.
6.10 Smart PLC Setting – RTC
RTU-EN01 has the independent Smart PLC function. The real-time clock (RTC) can be triggered by the system at
specific time. There are 16 RTCs in RTU-EN01. You can designate the trigger time or trigger the RTC on a
monthly, weekly or daily basis. Please refer to the explanations on RS#0 ~ RS#159.