Chapter 9 Troubleshooting
9-73
9_
Error code
Description
Corrective action
16#A015
A limit value set for channel 2 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 2 should be in the range of
-200000 to 200000.
16#A016
The interrupt number set for channel
2 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 2 should be in the
range of 0 to 31.
16#A021
The linear accumulation in channel 3
exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR56 to ON by means of FROM/TO.
16#A022
The scale set for channel 3 exceeds
the range.
Check the module parameter in HWCONFIG.
The scale set for channel 3 should be in the range of 0 to
32767.
16#A023
The number of cycles set for channel
3 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 3 should be in the
range of 2 to 60.
16#A024
The comparison value set for
channel 3 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 3 should be in the
range of -999999999 to 999999999.
16#A025
A limit value set for channel 3 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 3 should be in the range of
-200000 to 200000.
16#A026
The interrupt number set for channel
3 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 3 should be in the
range of 0 to 31.
16#A031
The linear accumulation in channel 4
exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR84 to ON by means of FROM/TO.
16#A032
The scale set for channel 4 exceeds
the range.
Check the module parameter in HWCONFIG.
The scale set for channel 4 should be in the range of 0 to
32767.
16#A033
The number of cycles set for channel
4 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 4 should be in the
range of 2 to 60.
16#A034
The comparison value set for
channel 4 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 4 should be in the
range of -999999999 to 999999999.
16#A035
A limit value set for channel 4 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 4 should be in the range of
-200000 to 200000.
16#A036
The interrupt number set for channel
4 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 4 should be in the
range of 0 to 31.

Table of Contents

Other manuals for Delta AH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AH Series and is the answer not in the manual?

Delta AH Series Specifications

General IconGeneral
BrandDelta
ModelAH Series
CategoryController
LanguageEnglish

Related product manuals