Amplon MX Series
z
z
06: Battery total AH setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
z
z
07: REPO logic setting
Parameter 2: Set up the REPO function control logic.
AO: Active Open (Default). When AO is selected as REPO logic, it will
activate REPO function with Pin 1 and Pin 2 in open status.
AC: Active Close. When AC is selected as REPO logic, it will activate REPO
function with Pin 1 and Pin 2 in close status.
z
z
08: Input Waveform Sensitivity setting