Chapter 11 Troubleshooting
65
Error
Code
Alarm
Message
Possible
Cause
Solution
0x1101
Output Overload
Shutdown
The UPS is over-
loaded.
Check the power
consumption of the
loads, and remove
the unnecessary
loads.
0xA000
Charger Fault
The UPS has an
internal fault.
Please contact
service personnel.
0x8106
,19,*%72YHU
Heat Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether the
vents are blocked.
2 Contact service
personnel.
0X6100
PFC Over Heat
Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether the
vents are blocked.
2. Contact service
personnel.
0x1003
Battery
Disconnected
1. The UPS is
not properly
connected to the
external battery
pack(s).
2. The battery/
batteries is (are)
damaged.
1. Check whether the
UPS is properly
connected to the
external battery
pack(s).
2. Contact service
personnel.
NOTE :
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.

Other manuals for Delta Amplon RT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Amplon RT Series and is the answer not in the manual?

Delta Amplon RT Series Specifications

General IconGeneral
BrandDelta
ModelAmplon RT Series
CategoryUPS
LanguageEnglish

Related product manuals