Chapter 8 : Operation
8.1 Start-up
NOTE :
1. Before start-up, ensure that the batteries are fully charged. Before
using the UPS for the first time, please check the battery capacity and
the charging settings. Make sure that you charge the batteries until the
battery capacity percentage shown on the UPS’s LCD is 100%
(
100
%
)
.
2. The configurable internal battery string quantity ranges from 16 to 22.
Please make sure that the actual quantity of battery strings are the same
DVWKDWFRQ¿JXUHGRQWKH/&'6HWXSWKHFRUUHVSRQGLQJFKDUJHFXUUHQW
based on the total battery amp-hour.
3. If the UPS connects to an inductive load, the inrush current (initial surge
current) may restart the inverter. To avoid this situation, please turn on the
inductive load in bypass mode before starting up the inverter.
z
Start-up with AC Input
1
9HULI\LIWKH836¶VLQSXWFRUGPHHWVZLWK1/*RIWKHZDOOVRFNHWDQGWKH
utility AC power works normally.
2
Switch on the input protective device (see
)LJXUH
) installed between
the UPS and the utility AC power. After that, the UPS will enter into the
Initial Setting Screen
(please refer to
,QLWLDO6HWWLQJ6FUHHQ
for more
information).
3
Press and hold
the ON/ OFF button
(
)
for 3 seconds to start up the
UPS. Release the button after you hear one beep and the UPS will start up.
After the UPS performs self-diagnosis, the UPS will run in
ON-LINE
mode.

Other manuals for Delta Amplon RT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Amplon RT Series and is the answer not in the manual?

Delta Amplon RT Series Specifications

General IconGeneral
BrandDelta
ModelAmplon RT Series
CategoryUPS
LanguageEnglish

Related product manuals