Chapter 9 LCD Display & Settings
49
You can choose the setup items such as Output, Input, ECO Mode, On/ Off
Settings, Battery, General, Outlet Control, Dry Contact Setting and Component
Life Prediction to set up relevant settings. For more information about the Setting
Menu, please refer to the tables below for each setup item’s relevant default value
and selectable value.
z
z
Output
Setup Items Selectable Value Default
Output Phase 1-phase 1-phase
Output Voltage
200V, 208V, 220V,
230V, 240V
208V for sux B8 model
230V for sux 35 model
Output Frequency
Auto* / Converter-50Hz** /
Converter-60Hz**
Auto
Output Sync.
Freq. Range
±0.5/ 1/ 3/ 5Hz ±3Hz
Output Freq.
Slew Rate
0.5/ 1/ 2/ 3/ 4 Hz/ sec. 1 Hz/sec.
Output Mode Industrial/ IT IT
Standby Mode No output/ Bypass output Bypass output
Overload Alarm 30-105% (one step: 5%) 105%
NOTE :
1. * When the Output Frequency is set as Auto, the output frequency
will vary according to the bypass frequency. If the bypass frequency
is ≥ 55Hz, the Free_Run_Frequency/ Cold_Start_Frequency will be
set as 60Hz.
If the bypass frequency is < 55Hz, the Free_Run_Frequency/ Cold_
Start_Frequency will be set as 50Hz.
2. When the Output Frequency is set as Auto and the Bypass Output
under the Standby Mode item is set as Enable, the bypass output
range will be the same as the Output Sync. Freq. Range.
3. ** When the Output Frequency is set as Converter-50Hz/
Converter-60Hz, the UPS will enter into Frequency Conversion
mode and the bypass output will become Disable.