50
Amplon RT Series
z
z
Input
Setup Item Selectable Value Default Value
Bypass Max. Voltage +10/ 15/ 20% +15%
Bypass Min. Voltage -10/ 15/ 20/ 25/ 30/ 35/ 40% -20%
z
z
ECO Mode
Setup Item Selectable Value Default Value
ECO Mode Disable/ Enable Disable
ECO Max. Voltage 5-15% (one step: 1%) +10%
ECO Min. Voltage 5-15% (one step: 1%) -10%
NOTE :
The setup items ECO Max. Voltage and ECO Min. Voltage will only be
shown on the display when ECO Mode is enabled.
z
z
On/ O󰀨 Settings
Setup Item Selectable Value Default Value
Energy Saving
Option 1*: Enable/ Disable
Option 2: 1-15mins (one step: 1min)
Option 3: 300W-1500W (one step: 100W)
Disable
Sleep Mode
Option 1: Enable/ Disable
Option 2: 10-120mins (one step: 10mins)
10mins
Auto Restart Enable/ Disable Enable
Auto Start on AC Enable/ Disable Disable
NOTE :
In Setting Menu, the sub item Option 1 under the item Energy Saving
cannot be changed.