Chapter 9 LCD Display & Settings
51
z
z
Battery
Setup Item Selectable Value Default Value
Automatic Battery Test
No test/ Daily/ Weekly/
Biweekly/ Monthly
No test
Deep Discharge Test 20-90% (one step: 10%) 90%
Low Battery
Warning Capacity
0-95%
(one step: 5%)
10%
Warning of
Remaining Time
0-60mins
(one step: 1min)
2mins
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240
(one step: 1min)
Disable
Charge Mode 2-stage/ 3-stage 2-stage
Float Charging
Voltage
Auto/ Customize
(2.20 - 2.35 V/ cell,
one step: 0.01V)
Auto
Internal Charging
Current
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6
1A (5K/ 6K)
1.5A (8K/ 10K)
External Battery Type *
Standard battery pack/
Customer own batt. pack
External Battery
Capacity
Standard battery pack:
Part Number Quantity
Customer own batt. pack:
Battery Voltage Capacity
Install date YYYY/ MM/ DD
NOTE :
* When the External Battery Type is set as Standard battery pack, you
need to configure the Part Number and the Quantity of the standard
battery pack(s).