Chapter 12 Troubleshooting
12-29
12_
Error
code
Description
CPU
status
ERROR LED indicator status
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
600D
RJ45 port is not connected.
Continue
V
6010
The number of the MODBUS TCP connections
exceeds the range.
Continue V
6011
The number of the EtherNet/IP connections
exceeds the range.
Continue V
6012 There are devices using the same IP address. Continue V
6100
The email connection is busy.
Continue
V
6103
The trigger attachment
mode in the email is set
incorrectly.
Continue V
6104
The attachment in the email does not exist.
Continue
V
6105
The attachment in the email is too big.
Continue
V
6106
There is an SMTP server response timeout.
Continue
V
6107
There is an SMTP server response timeout.
Continue
V
6108
SMTP verification failed
Continue
V
6200
The remote communication IP address
set in the
TCP socket function is illegal.
Continue V
6201
The local communication port set in the TCP socket
function is illegal.
Continue V
6202
The remote
communication port set in the TCP
socket function is illegal.
Continue V
6203
The device from which the data is sent in the TCP
socket function is illegal.
Continue V
6206
The device that
receives the data in the TCP socket
function is illegal.
Continue V
6208
The data that
is received through the TCP socket
exceeds the device range.
Continue V
6209
The remote communication IP address
set in the
UDP socket function is illegal.
Continue V
620A
The local communication port set in the UD
P socket
function is illegal.
Continue V
620C
The device from which the data is sent in the UD
P
socket function is illegal.
Continue V
620F
The device that receives the data in the UD
P socket
function is illegal.
Continue V
6210
The data that is received through the UD
P socket
exceeds the device range.
Continue V
6212
There is no response from the remote device after
the timeout period.
Continue V
6213 The data received exceeds the limit. Continue V
6214
The remote device refuses the connection.
Continue
V
6215
The socket is not opened.
Continue
V
6217
The socket is opened.
Continue
V
6218
The data has been sent through the socket.
Continue
V
6219
The data has been received through the socket.
Continue
V
621A
The socket is closed.
Continue
V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS300 Series and is the answer not in the manual?

Delta AS300 Series Specifications

General IconGeneral
BrandDelta
ModelAS300 Series
CategoryControl Unit
LanguageEnglish

Related product manuals