Chapter 6 Control Mode of Operation ASDA-A2R Series
6-14 Revision December, 2014
Manual Setting:
There are two sets of low-frequency vibration suppression. One is parameter
P1-25~P1-26 and another one is parameter P1-27~P1-28. These two sets of
low-frequency vibration suppression can be used to eliminate two different frequency
vibration. Parameter P1-25 and P1-27 are used to suppress the low-frequency vibration.
The function is working only when the parameter setting value of low-frequency vibration
close to the real vibration frequency. Parameter P1-26 and P1-28 are used to set the
response after filter. The bigger the setting value of P1-26 and P1-28 is, the better
response will be. However, if the value is set too big, the motor might not operate
smoothly. The default value of parameter P1-26 and P1-28 is 0, which means the
function is disabled.
Related parameters: Please refer to Chapter 8 for further information.
Parameter Abbr. Function
P1-25 VSF1 Low-frequency Vibration Suppression (1)
P1-26 VSG1 Low-frequency Vibration Suppression Gain (1)
P1-27 VSF2 Low-frequency Vibration Suppression (2)
P1-28 VSG2 Low-frequency Vibration Suppression Gain (2)